ZR-KVVP, ZR-KYJVP flame retardant control cable
Description
ZR-KVVP, ZR-KYJVP flame retardant control cable
Executive standard
GB/T 9330-2008 plastic insulated control cable
General rules for GB/T19666-2005 flame retardant and fire resistant wire and cable
purpose
Plastic insulated (PVC insulated and XLPE insulated) sheath control cables are used for occasions such as AC rated voltage 0.6/1kV, 450/750V control, monitoring circuit and protection circuit, etc., for power distribution and control of power plants and substations in power plants and substations, and for use in flame retardant requirements.
Name of other flame retardant cables
Type number | Name |
ZR-KVV | Copper core PVC insulated PVC sheathed flame retardant control cable |
ZR-KYJV | Copper core XLPE insulated PVC sheathed flame retardant PVC control cable |
ZR-KVVP | Copper core PVC insulated braided shielding flame retardant control cable |
ZR-KYJVP | Copper core XLPE insulated copper wire braided shielded PVC sheathed flame retardant control cable |
ZR-KVVP2 | Copper core PVC insulated copper tape shielded PVC sheathed flame retardant control cable |
ZR-KYJVP2 | Copper core XLPE insulated copper tape shielded PVC sheathed flame retardant control cable |
ZR-KVVP3 | Copper core PVC insulated copper tape shielded PVC sheathed flame retardant control cable |
ZR-KYJVP3 | Copper core XLPE insulated copper tape shielded PVC sheathed flame retardant control cable |
ZR-KVV22 | Copper core PVC insulated steel tape armoured PVC sheathed flame retardant control cable |
ZR-KYJV22 | Copper core XLPE insulated steel tape armored PVC sheathed flame retardant control cable |
ZR-KVV32 | Copper core PVC insulated fine steel wire armoured PVC sheathed flame retardant control cable |
ZR-KYJV32 | Copper core XLPE insulated fine steel wire armoured PVC sheathed flame retardant control cable |
ZR-KVVP2-22 | Copper core PVC insulated copper tape shielded steel tape armored PVC sheathed flame retardant control cable |
ZR-KYJVP2-22 | Copper core XLPE insulated copper tape shielded steel tape armored PVC sheathed flame retardant control cable |
ZR-KVVR | Copper core PVC insulated PVC sheathed control flexible cable |
ZR-KVVRP | Copper core PVC insulated copper wire braided shielded PVC sheathed control flexible cable |
DDZ-KVV | Copper core PVC insulated PVC sheathed low halogen low smoke flame retardant control cable |
DDZ-KVVP | Copper core PVC insulated braid shielded low halogen low smoke flame retardant control cable |
DDZ-KVVP2 | Copper core PVC insulated copper tape shielded low halogen low smoke flame retardant control cable |
DDZ-KVV22 | Copper core PVC insulated steel tape armored low halogen low smoke flame retardant control cable |
DDZ-KVV32 | Copper core PVC insulated fine steel wire armored low halogen low smoke flame retardant control cable |
WDZ-KYJY | Copper core XLPE insulated halogen free low smoke flame retardant control cable |
WDZ-KYJYP | Copper core XLPE insulated braided shielding sheath halogen free low smoke flame retardant control cable |
WDZ-KYJYP2 | Copper core XLPE insulated copper tape shielded halogen free low smoke flame retardant control cable |
WDZ-KYJY23 | Copper core XLPE insulated steel tape armored halogen free low smoke flame retardant control cable |
WDZ-KYJY33 | Copper core XLPE insulated fine steel wire armored halogen free low smoke flame retardant control cable |
Note: flame retardant (ZR) is divided into bundles A, B, C flame retardant, respectively, ZA, ZB and ZC, generally do not specify (ZR) level is C class, plus WDZ for low smoke halogen free cable.
Product specification
Table 2
Type number | rated Voltage V | Guide body nominal section mm2 | ||||||||
Zero point five | Zero point seven five | One | One point five | Two point five | Four | Six | Ten | |||
The rated voltage is U0/U 450/750V.
The long term allowable working temperature of PVC insulated conductor is 70 C; the long-term allowable working temperature of XLPE insulated conductor is 90 C;
The laying temperature of the cable should not be less than 0 degrees. The recommended allowable bending radius is:
The cable without armored layer should not be less than 6 times of the outer diameter of the cable.
The cable with armored or copper shielded structure shall be not less than 12 times the outer diameter of the cable.
The soft cable with shielding structure should be not less than 6 times the cable.
By color recognition, the insulation cores of 5 core and below cables are colored or digital.
By digital recognition, from the inner layer to the outer layer, it starts clockwise in the order of natural numbers starting from 1, and the color of the digital logo should be obviously different from the insulation color.
Main technical specifications of cables
1. When the conductor is 20 degrees, the large DC resistance is shown in Table 3.
Table 3 large DC resistance / Omega /km at 20 degree conductor
Nominal cross section of conductor Mm2 | Conductor category | ||
1 kinds | 2 kinds | 5 kinds | |
Large DC resistance of 20 /km | |||
Zero point five | Thirty-six | Thirty-six | Thirty-nine |
Zero point seven five | Twenty-four point five | Twenty-four point five | Twenty-six |
One | Eighteen point one | Eighteen point one | Nineteen point five |
One point five | Twelve point one | Twelve point one | Thirteen point three |
Two point five | Seven point four one | Seven point four one | Seven point nine eight |
Four | Four point six one | Four point six one | Four point nine five |
Six | Three point zero eight | Three point zero eight | Three point three zero |
Ten | One point eight three | One point eight three | One point nine one |
2. AC withstand voltage test for power frequency is shown in Table 4.
Table 4 voltage test
Rated working voltage Item | 450/750V | |
AC voltage frequency Test time Test voltage test result | 50Hz 5 minutes 3000V No breakdown | 50Hz 5 minutes 3500V No breakdown |
3. Insulation resistance at working temperature is shown in Table 5.
Table 5 insulation resistance at a permissible operating temperature
Nominal cross section of conductor Mm2 | Small insulation resistance M Omega.Km | ||||
PVC insulation (70 C) | XLPE insulation (90 C) | ||||
1 kinds | 2 kinds | 5 kinds | 1 kinds | 2 kinds | |
Zero point five | - | - | Zero point zero one three | - | - |
Zero point seven five | Zero point zero one two | Zero point zero one four | Zero point zero one one | One point two | One point four |
One | Zero point zero one one | Zero point zero one three | Zero point zero one zero | One point one | One point three |
One point five | Zero point zero one one | Zero point zero one zero | Zero point zero one zero | One point one | One |
Two point five | Zero point zero one zero | Zero point zero zero nine | Zero point zero zero nine | One | Zero point nine |
Four | Zero point zero zero eight five | Zero point zero zero seven seven | - | Zero point eight five | Zero point seven seven |
Six | Zero point zero zero seven zero | Zero point zero zero six five | - | Zero point seven zero | Zero point six five |
Ten | - | Zero point zero zero six five | - | - | Zero point six five |
4, flame retardancy
The flame-retardant properties should be tested by A, B or C in the prescribed burning of GB/T18380.33 ~ 35. If the user fails to make a request, according to the requirements of the C test, it will meet the requirements specified in Table 6.
Table 6 requirements for bunched combustion
Code name | Volume of test metal material (L/m) | Fire time /min | Conformity index |
ZA ZB ZC ZD* | Seven Three point five One point five Zero point five | Forty Forty Twenty Twenty | 1) the length of carbon is not greater than 2.5m. 2) after the fire is stopped, the trapping time is less than 1 hours. |
ZD - only for wires and cables whose outer diameter is less than 12mm. |