Explosion proof thermal resistance
Description
Product overview
The explosion-proof thermal resistance is used as a sensor for measuring and controlling the temperature and matching with the display instrument, so as to directly measure and control the temperature of gas, liquid and steam in the production process. The explosion-proof performance of the special explosion-proof type thermal resistor and explosion proof thermocouple products manufactured by our company is designed and manufactured according to the standards of "explosive environmental explosion-proof electrical equipment" promulgated by the state. The thermoelectric characteristics conform to the international IEC standard and are qualified by the national instrument explosion proof safety supervision station. The structure and principle of the explosion-proof thermal resistor are basically the same as that of the assembly. The main difference is that the design of the flameproof product junction box (shell) is made of high strength aluminum alloy die-casting, and has enough internal space, wall thickness and mechanical strength. The thermal stability of the rubber sealing ring accords with the national explosion-proof standard. Therefore, when the explosive mixture gas exploded inside the junction box, the internal pressure will not destroy the junction box, and the heat generated therefrom can not diffuse outwards. It detonating. As long as the user strictly follows the rules of product use, the explosion-proof thermal resistance product can achieve a reliable explosion-proof effect.
Characteristics:
The pressure spring type temperature sensing element has good anti vibration performance.
The measurement accuracy is high.
There is no need to compensate the conductor to save money.
Imported film resistors are reliable and stable.
Working principle:
The explosion-proof thermal resistor is designed by using the gap flameproof principle to design components with enough strength, such as junction boxes. All components that generate sparks, arcs and dangerous temperatures are sealed in the junction box. When the cavity explode, the flame and temperature can not be transmitted outside the cavity through the joint gap clearance and cooling.
Main technical parameters:
Product execution standard
IEC751 JB/T18622-1997 JB/T8623-1997 JB/T5518-91
Ambient temperature insulation resistance
The explosion-proof thermal resistance is at 15 to 35 degrees C, and the relative humidity is not greater than 80%. The test voltage is 10 - 100V (DC), the insulation resistance between the electrode and the outer tube is 100M ohm.
Measuring range and tolerance
Model | Graduation | Measuring range | Accuracy grade | Allowable error |
WZP | Pt100 | -200-+500 | Class A | (0.15+0.002) LTL |
Level B | (0.30+0.005) LTL | |||
WZC | Cu50 Cu100 | -50-+100 | --- | (0.30+0.005) LTL |
Model naming method
W | Temperature instrument | |||||||
A kind of | Z | Thermal resistance | ||||||
A kind of | Grading of temperature sensor material | |||||||
P | Pt Pt100 | |||||||
A kind of | Logarithm of even filament | |||||||
nothing | Single branch | |||||||
A kind of | Install fixed form | |||||||
One | No fixed device | |||||||
A kind of | Junction box form | |||||||
Four | Explosion proof type | |||||||
A kind of | Diameter of protection tube | |||||||
Zero | Phi 16 | |||||||
A kind of | Working end form | |||||||
G | variable cross-section | |||||||
A kind of | ||||||||
W | Z | P | 2 - | Two | Four | Zero | G | Examples of typical models |
Selection notes
1) model
2) indexing number
3) explosion-proof rating
4) accuracy level
5) installation and fixation
6) protective tube material
7) length or insertion depth
Case A: explosion-proof thermistor, type Pt100, fixed thread M27 * 2, explosion proof grade D II BT4 level, protection tube 316, insertion depth 300mm. The model is WZP-240, Pt100, D II BT4, thread M27 x 2, protection tube 316, L=450 x 300mm.